NYCY 0.6/1kV Cable: What Is Concentric Copper Screen (CWS) Cable
NYCY is a popular European standard low voltage power and control cable, rated at 0.6/1kV. Its full designation is Cu/PVC/CWS/PVC, which means copper conductor, PVC insulation, concentric copper wire screen and outer PVC sheath. Unlike ordinary PVC power cables, the built-in concentric copper screen is its most distinctive feature, bringing both EMC shielding and protective earth functions in one design.
What Is the Structure of NYCY Cable?
The construction of NYCY follows VDE 0276-603 and IEC 60502-1 standards:
- Solid or stranded plain copper conductor (Class 1 / Class 2)
- PVC insulation (70°C maximum continuous operating temperature)
- Concentric copper wire screen (CWS, helical copper wires plus copper tape)
- PVC outer sheath, usually black This concentric copper layer wraps evenly around the insulated cores. It can work as a neutral conductor, protective earth conductor and electromagnetic shield at the same time. That is why NYCY is widely chosen for projects requiring reliable earthing and noise suppression.
Key Benefits of NYCY Concentric Screen Cable
First, the integrated CWS layer simplifies installation. You do not need to run a separate earth wire for many fixed distribution layouts. It reduces wiring workload and saves space inside cable ducts. Second, the copper screen suppresses electromagnetic interference. It protects control signals and power circuits from external noise, which matters for factory automation, lighting control and monitoring systems. Third, PVC insulation and sheath offer good resistance to moisture and moderate chemical exposure. The cable suits dry and wet locations, indoors, outdoors, in ducts and direct underground burial, as long as there is no heavy mechanical impact. Finally, NYCY is a cost-effective VDE standard solution. Compared with armoured cables, it has smaller outer diameter and lower weight for fixed power distribution tasks.
Common Applications of NYCY 0.6/1kV Cable
NYCY is designed for fixed installation. Typical use cases include:
- Industrial plant power distribution and control circuits
- Street lighting and traffic signal power supply
- Local low-voltage utility networks and building service connections
- HVAC and pump control systems
- Substation auxiliary power and monitoring wiring
It is important to note that NYCY is not armoured. You should select NYBY if the route risks sharp rock, heavy compression or rodent damage. If you need higher temperature resistance instead of PVC insulation, N2XY (XLPE insulated) will be the proper alternative.
Installation Tips
- Minimum bending radius for fixed installation: 7 × cable overall diameter
- Long-term rated conductor temperature: 70°C
- Suitable for direct burial, cable ducts, wall conduits; not for free flexible moving use
- Follow local wiring codes when using the concentric screen as protective earth
FAQ
Q: What does CWS stand for in NYCY Cu/PVC/CWS/PVC? A: CWS means Concentric Wire Screen, the helical copper wire layer between insulation and outer sheath.
Q: What is the difference between NYCY and NYBY? A: NYCY has concentric copper screen; NYBY has steel tape armour for mechanical protection. NYCY focuses on EMC and earthing, NYBY focuses on crush and impact resistance.
Q: Can NYCY be buried directly? A: Yes, direct burial is allowed, but extra protection is required where mechanical damage may occur.
Q: NYCY vs N2XY? A: NYCY is PVC insulated (70°C). N2XY uses XLPE insulation and runs up to 90°C, better for higher load and heat conditions.
Wrap Up
NYCY fills a unique niche in low-voltage cabling. Its all-in-one concentric copper screen makes it ideal for power + control circuits where EMC protection and simplified earthing are priorities. If you are sourcing standard VDE concentric screen power cables, WireNexis supplies NYCY 0.6/1kV cables with full size options and technical test reports.